Fire doors only work if they are fitted, maintained and used correctly. A door that does not close, has damaged seals or large gaps, or has been altered without care, may not hold back fire and smoke for long enough to protect an escape route. Ashworth Fire Consultancy carries out non-intrusive visual fire door surveys, giving you a clear record of the condition of your doors and what needs to be done.
What the survey includes
Each door within the agreed scope is inspected visually from both sides where access allows. We record what can be seen without removing the door, its ironmongery or the surrounding construction. Typical points examined include:
- whether the door closes fully and latches from any angle of opening, where a self-closing device is fitted
- gaps between the door leaf and frame, and at the threshold
- the condition of intumescent strips and smoke seals, where fitted
- hinges, latches, locks and other hardware, including missing or loose fixings
- any glazing, vision panels and air transfer grilles
- visible certification marks or labels, where present
- damage, alterations or unsuitable repairs to the leaf or frame
- the condition of the frame and the visible junction with the wall
- appropriate signage
- whether doors are wedged or held open without a suitable release device
What you receive
- A door register: a list of every door inspected, its location and its condition.
- Photographic evidence for each door, showing the issues found.
- A clear remedial action plan, so that you or your contractor can see what is needed and plan the work.
Remedial work should be carried out by a competent person. We set out what is needed in plain English so you can brief a contractor and check that the outcome has been achieved.
Fire doors in residential buildings
In blocks of flats, the flat entrance doors and the doors on the common escape routes protect residents while they escape, or while they remain in their flats under a "stay put" strategy.
In England, the Fire Safety (England) Regulations 2022 require responsible persons in buildings with two or more flats where the top storey is above 11 metres to check communal fire doors at least every 3 months and to use best endeavours to check flat entrance doors at least every 12 months, including self-closing devices, and to record the steps taken to gain access. Government guidance says these routine checks are basic visual checks that suitably instructed staff can carry out. A fire door survey is a more detailed assessment and does not replace them. The duty to give residents fire door information applies to all blocks with two or more flats and common parts, regardless of height.
This page describes the law in England (and, where stated, Wales). Scotland (Fire (Scotland) Act 2005) and Northern Ireland (Fire Safety Regulations (Northern Ireland) 2010) have different legislation. Wales is not covered by the Fire Safety (England) Regulations 2022.
A survey can give you a baseline, help you identify doors that need repair or replacement, and support your ongoing checking regime.
Commercial and other premises
Fire doors are just as important in offices, shops, warehouses, schools, care settings and places of assembly. A survey can be carried out alongside a commercial fire risk assessment or on its own, for example after a refurbishment or as part of a planned maintenance programme.
Limits of a non-intrusive survey
A visual survey records what can be seen. It does not involve removing doors, hardware or architraves, and it cannot confirm hidden details such as the internal construction of the leaf or how the frame is fixed and sealed into the wall. Where the visible evidence raises doubts that can only be resolved by intrusive investigation or by manufacturer's evidence, we will say so in the report.
Who carries out the survey
Surveys are carried out by Bradley Ashworth.
- More than ten years in fire safety.
- BSc (Hons) Fire & Leadership Studies.
- National Fire Risk Assessors Register, Advanced level (registration 1685).
- Associate Member of the Institution of Fire Engineers (AIFireE).
- Member of the Institute of Fire Safety Managers (MIFSM).
Areas we cover
From our base in Widnes we cover Widnes and Halton, Cheshire, Liverpool and Merseyside and Manchester and Greater Manchester, and we work across the UK.
Frequently asked questions
Do you need access to both sides of flat entrance doors?
Ideally, yes. Where we can only see one side, we record this in the register. Access to flats is arranged in advance with the landlord or residents.
Do you fix the doors?
No. We survey and report. Remedial work should be carried out by a competent contractor.
Is a fire door survey the same as a fire risk assessment?
No. A fire risk assessment considers fire safety in the premises as a whole, including fire doors at a general level. A fire door survey records the condition of each door in detail.
How often should fire doors be checked?
It depends on the building and how the doors are used. In England, the Fire Safety (England) Regulations 2022 set minimum check frequencies for residential buildings where the top storey is above 11 metres. Heavily used doors may need more frequent checks.
Can you survey a sample of doors rather than all of them?
The scope is agreed with you. A full survey gives the most complete record, but we can discuss a sample where that suits your needs.